following the procedure of the Air Velocity
- This test is performed to determine the air flow supply rate in non unidirectional clean room and the air velocity distribution in a unidirectional clean room.
-Typically either airflow velocity or airflow rate testing will be performed and results will measured in average velocity, average air flow rate or total air flow rate.
-Total airflow rate may in turn be used to determine the exchange rate (in change per hour) for non unidirectional installation.
-Air velocity test is performed to measure the Velocity of air supplied by the AHU. By using the Air velocity Air change per hour can be count.
-Air changes per hour (ACPH) mean the volume of air supplied to a room, in m3/hr, divided by the room volume, in m3.
-Test is carried out by using calibrated anemometer.
-Anemometer should be sanitized with 70% IPA along with its carrying case and connecting cables.
-The anemometer should be handled in such a way that it will not obstruct air supply.
- Filter area should be divided into grids of equal filtration zones.
-The reading should be taken approximately 6 inch from the surface of the grill at its centre and corners.
-Measure the velocity and record the reading.
S1
|
S2
|
|||
1 2
5
4 3
|
1 2
5
4 3
|
|||
B
|
||||
A
|
Where, S1, S2 are supply air ducts of dimensions A x B respectively.
-The air supply volume is calculated as follows:
-The air supply volume is calculated as follows:
Air Supply Volume = Mean air velocity (FPM) X Grill Area (Ft2)
=______CFM
-Where mean air velocity is the average of all velocity readings of the filter.
-Air Changes per Hour (ACPH) = Air supply volume (CFM) x 60
Room Volume (ft3)
-Minimum Air Changes per Hour shall meet the acceptance criteria.
-If not, HEPA filter shall be checked, flow shall be adjusted as necessary or if required HEPA filter shall be replaced.
-Any corrective action taken as a result of investigation shall be recorded. Major changes to air supply system must be undertaken by authorized personnel only.
- Filter integrity ,Non viable particle count , Recovery Test are the another important test to perform the HVAC Validation.
No comments:
Post a Comment